Ex wireless pull-wire switch Ex RF 95 WH/90° EN868

Features/Options

  • Ex zone 1 and 21
  • Thermoplastic enclosure
  • Horizontally slotted mounting holes
  • Mounting details to EN 50047
  • Output signal can be individually configurated at the receiver
  • EnOcean® wireless technology
  • No power supply, no wiring and pipe laying required
  • Multi-network capable
  • Easy programming of receiver

Technical data

StandardsEN 60947-5-1; EN 61000-6-2;
EN 301 489-1; EN 301 489-3;
EN 300 220-3; EN 60079-0;
EN 60079-11; EN 61241-11
Enclosureglass-fibre reinforced, shock-proof thermoplastic (PA 66), self-extinguishing UL 94-V0
Coverglass-fibre reinforced, shock-proof thermoplastic (PA 66), self-extinguishing UL 94-V0
Degree of protectionIP 65 to IEC/EN 60529
ProtocolEnOcean®
Ambient temperature–20 °C … +65 °C
Operation cyclesapprox. 9000 telegrams at repetitions/h
Voltage supplyElectrodynamic energy generator
Frequency868.3 MHz
Transmission powermax. 10 mW
Data rate120 kbps
Channel bandwidth280 kHz
Sensing rangemax. 300 m outside,
max. 30 m inside
Mechanical life> 1 million operations
Actuating timemin. 80 ms
Impact energymax. 7 J
Noteno status signal available
Ex marking II 2G Ex ib IIC T6 Gb
II 2D Ex ib IIIC T80 °C Db
IECEx Ex ib IIC T6 Gb
Ex ib IIIC T80 °C Db
ApprovalsBVS 08 ATEX E 111
IECEx BVS 08.0048
Ordering details
Type code